Power cables suitable for laying in open air, in ground, in cable trays and ducts, in areas with high risk of mechanical damages are not expected. 

Parametrs

Exploitation temperature range °C from -50 to 50
Short-circuit temperature °C 160
Bending radius 12D
Fire properties EN 60332-1-2
Operating conductor temperature °C max +70
Cabling (inside/outside) inside/outside
Installation temperature °C -5
Frequency, Hz 50
Testing voltage, kV 4
Rated voltage, kV 0,6/1
NYCY, DIN VDE 0276-603, HD 603, IEC 60502-1 - фото - 1
NYCY, DIN VDE 0276-603, HD 603, IEC 60502-1 - фото - 1

Power cables suitable for laying in open air, in ground, in cable trays and ducts, in areas with high risk of mechanical damages are not expected. 

Parametrs

Exploitation temperature range °C from -50 to 50
Short-circuit temperature °C 160
Bending radius 12D
Fire properties EN 60332-1-2
Operating conductor temperature °C max +70
Cabling (inside/outside) inside/outside
Installation temperature °C -5
Frequency, Hz 50
Testing voltage, kV 4
Rated voltage, kV 0,6/1

Construction

  1. Conductor: Copper acc. to EN 60228, Class 1 - RE (solid, round);
  2. Insulation: PVC (color code acc. to HD 603 clause 4);
  3. Filler/inner covering: EPDM+PVC or PVC;
  4. Screen: Copper wires and copper tape, applied helically;
  5. Cover: PVC sheath (black color)

Cable sizes

Numbers of conductors 1-61
Minimum conductor size, mm2 1,5
Maximum conductor size, mm2 16